Retrotec Blower Door telpu hermētiskuma pārbaudei (Integrity Test)

EU6110X-F augstspiediena Blower Door

Ražotājs: Retrotec
Produkta kods: EU6110X-F

EU6110X-F Integrity System

To see if dampers really have the vent area they claim to have, they need to be tested and this model does that really well. It not only has lots of flow but can create 100s of Pa to see at what point the Pressure Relief Vents actually open. Then it will test the vent path to ensure the peak pressure evaluation complies with the standard.

Sufficient power also to test larger enclosures and an ideal place to start since it can be easily upgraded to the full feature 3212F when you want to measure the lower leak which often is the only way to pass many enclosures.

Test for hold times in flooded volumes up to 51,000 cu ft (1000 m3) for Inert agents and 70,000 cu ft (2000 m3) for halocarbon chemical agents.

Testing pressure relief vents will require more power. This system will test the venting for a volume up to a maximum of 12,000 cu ft (330 m3) for Inert agents although vents up to 8 sq ft (0.8 m2) can be measured individually.

Request literature on all of Retrotec systems to determine the size of enclosures that can be tested with each system.

Why Retrotec for Enclosure Integrity?

All Retrotec systems include tech support from Retrotec who originated the idea of Enclosure Integrity testing in 1984. They promoted it within NFPA and in 1986 wrote the first Enclosure Integrity standard. Retrotec has been the lead researcher for enclosure testing ever since.  Every major clean agent system manufacturer worldwide relies on Retrotec’s expertise for both hold time and peak pressure predictions.

 

Model 6000 Fan

 

Flow Into:

M3/h

Max Flow, per fan (60 Hz)

Reduces values by 15% for 50Hz fan

Free Air

13,762

50 Pa

13,082

Minimum Flow:

 

 

on Included Range B1

50 Pa

161

on Optional Range 74

50 Pa

63

on Optional Range 47

50 Pa

35

on Optional Range 29

50 Pa

15

Dimensions:

55.9 cm inlet diameter, 24.8 cm long, 63.5 cm height

Weight:

15.2 kg or 16.0 kg with Ring A & Plated B8 installed

Flow Accuracy:

+/-5%

Power:

240V@50hz/4.9A

Recommended Fan Calibration Interval:

5 years

 

* The max flow of the fan will vary depending on the following factors: Voltage, frequency, barometric pressure, back pressure, blade pitch, air temperature, bearing tightness, inlet air turbulence


* 5000/6000 series blower doors DO NOT work with the DM-2 digital gauge